Published on July 11, 2026 at 6:56 pm
A service technician is standing in front of a chemical reactor. The central process control system shows „Pressure out of tolerance“ for the reactor. The installed pressure sensor should be measuring 4 bar and, via a transmitter, putting a 12 mA signal on the 4-20 mA line (for a 0-8 bar range). But the HMI screen reads „3.2 bar“, which would correspond to a 10.4 mA signal. That is a discrepancy of 1.6 mA between what the sensor should be sending and what actually arrives.
Where is the fault? There are four possible causes:
- The ACTUAL PRESSURE IS 3.2 bar (a process problem, not a measurement error).
- The PRESSURE SENSOR is defective and reporting incorrectly.
- The 4-20 mA TRANSMITTER is converting incorrectly.
- The PLC INPUT is misinterpreting the mA signal.
Without a systematic diagnosis, it is impossible to know which point in the chain is failing. You could test all four components, but that takes hours. With a precision current/voltage calibrator such as the Extech PRC15, the technician can substitute each point in the chain individually and isolate the fault in 5 minutes.
What a Process Calibrator Actually Is
A calibrator is an instrument that generates or measures a CONTROLLED ELECTRICAL SIGNAL. For 4-20 mA process signals, the PRC15 has two operating modes:
SOURCE mode: The instrument BECOMES a simulated sensor. It sends a precisely set current (0-24 mA) on a line. Two-wire circuit, so that it behaves like a real 4-20 mA transmitter.
MEASURE mode: The instrument replaces a PLC input or an HMI. It MEASURES the current arriving on a line.
Diagnostic application: break the signal path at one point, replace that point with the calibrator, then test in both directions.
The Fault Isolation Procedure
Back to the reactor example. The technician proceeds as follows:
Step 1: Sensor test. He disconnects the pressure sensor from the transmitter and connects his PRC15 in MEASURE mode. He applies a known reference pressure to the sensor (e.g. 4.0 bar from a test pressure gauge). The sensor should deliver a 12.0 mA output signal. If it does → sensor OK. If not → replace the sensor.
Step 2: Transmitter test. He disconnects the transmitter from the cable and connects his PRC15 in SOURCE mode as a „sensor substitute“. He sets 12.0 mA and feeds it into the transmitter input. The transmitter should pass 12.0 mA on to its output. If it does → transmitter OK. If not → replace the transmitter.
Step 3: Cable test. With the PRC15 in MEASURE mode, he measures what arrives at the far end of the cable while feeding 12.0 mA in at the near end. If the values match → cable OK. If there is a discrepancy → cable fault.
Step 4: PLC input test. He feeds 12.0 mA from the PRC15 directly into the PLC input. He observes what the HMI displays. If 4.0 bar → PLC OK. If a different value → PLC configuration or hardware fault.
Total time: 15-25 minutes. Fault isolation guaranteed. Without such an instrument: hours of trial-and-error debugging, often replacing several components „on suspicion“.
Why 4-20 mA and Not 0-10 V?
Process signals mainly use 4-20 mA CURRENT (not 0-10 V VOLTAGE). The PRC15 supports both, but 4-20 mA is the industrial standard for three reasons (which I already touched on in the IRIS refractometer article):
- Cable length tolerance: Current stays constant over any length (no voltage drop).
- EMC tolerance: Current signals are less susceptible to electromagnetic interference.
- Fault detection: On a wire break → 0 mA (not 4 mA!). The PLC detects hardware faults directly, without wrongly assuming a „0% value“.
The PRC15’s 0-24 mA range covers the full 4-20 mA process range plus „-25%“ (0 mA for wire-break simulation) and „+125%“ (24 mA for saturation testing).
The 5 User Presets
The PRC15 has 5 storable presets. Typical use:
- Preset 1: 4.00 mA — 0% of process range, „empty state“ test.
- Preset 2: 8.00 mA — 25% of process range, intermediate value test.
- Preset 3: 12.00 mA — 50% of process range, midpoint test.
- Preset 4: 16.00 mA — 75% of process range, upper intermediate value.
- Preset 5: 20.00 mA — 100% of process range, „full“ test.
When diagnosing faults, the technician can quickly cycle through all 5 values (5-point linearity test) instead of manually setting each mA value. Test duration per loop of 3-5 minutes instead of 15+ minutes.
Battery and Mains Power
The PRC15 can be powered by:
- 6 x AA batteries (standard alkaline): ~40 hours of operation.
- 100-240 V universal AC adapter (with 4 plug types — US, EU, UK, AU): unlimited operation.
Why both options? Fieldwork often requires battery operation (no power outlet at the reactor). Workshop calibration often requires continuous operation (several hours of test series). The PRC15 covers both scenarios.
Areas of Application
Commissioning of new systems: When installing a new sensor/transmitter, the PRC15 is used to test the full 4-20 mA chain before the process goes live.
Fault diagnosis on running systems: For „sensor is delivering wrong values“ reports, isolate the cause without replacing several components „on suspicion“.
Regular calibration of transmitters: Under EN ISO 9001, process instruments must be verified periodically. The PRC15 serves as the reference.
PLC and HMI configuration: With new software setups, the technician can feed in values and verify that the HMI shows the correct readings.
Control loop testing: With PID control, you can use the PRC15 to feed in simulated actual values and observe how the controller responds.
Testing alarms: Limit-value alarms can be verified by simulating an alarm value (e.g. 22 mA).
Training: A standard teaching aid in vocational schools for measurement and control technology.
What the PRC15 Cannot Do
- Higher currents (above 24 mA): For 10 A DC currents or AC currents, you need a multimeter with a current clamp.
- Higher voltages (above 20 V): For 100 V or 400 V systems, you need higher-range calibrators.
- HART communication: Modern „smart“ transmitters communicate via the HART protocol on the 4-20 mA line. The PRC15 does not emulate HART.
- Frequency simulation: For encoder testing or frequency converters, you need a frequency signal generator.
- Temperature simulation: For thermocouple or PT100 testing, you need a temperature calibrator (special version).
The PRC15 is the core tool for 4-20 mA / 0-20 V work — other signals require complementary instruments.
Comparison with More Expensive Alternatives
Extech PRC15 (this one): 701 EUR. 4-20 mA + 0-20 V. Handheld. Basic accuracy ±0.02%.
Fluke 705 Loop Calibrator: 850-1,200 EUR. Similar function, premium brand.
Fluke 754 Documenting Process Calibrator: 3,500-5,000 EUR. Additionally: HART communication, documentation function, multiple signal types.
Beamex MC6: 8,000-15,000 EUR. Premium class with multiple channels and reporting.
The PRC15 is the economical entry into professional process calibration. Sufficient for 90% of industrial maintenance requirements.
What You Get for Your Money
Extech PRC15 precision current/voltage calibrator, 0-24 mA output/measurement (covers -25% to +125% of the 4-20 mA process range), 0-20 V DC output/measurement, 5 storable user presets for quick access to frequently used test values, backlit LCD, standard banana I/O ports for flexible wiring, palm-size double-molded housing with field protection, 6 x AA batteries for ~40 hours of handheld operation, 100-240 V universal AC adapter with 4 plug types for continuous operation, test leads with alligator clips included, hard-shell carrying case. 701 EUR.
A standard tool for industrial maintenance technicians, commissioning engineers, calibration lab personnel and electrical instrumentation technicians. In systems with 20+ process signals, it pays for itself quickly through the time saved on fault diagnosis — every avoided „on suspicion“ replacement saves several hundred EUR and hours of production downtime. Not suitable for higher currents, higher voltages or HART communication, but for the core of 4-20 mA maintenance work it is the economical sweet-spot choice.