Grounding is the silent safety mechanism in every electrical installation. It goes unnoticed as long as it works — and when it fails, this only becomes apparent during a fault, often with fatal consequences. This is why earth resistance testing is mandatory: under DIN VDE 0100, every new installation must be tested before commissioning, and under DGUV Regulation 3, the test is repeated at least every four years for fixed installations. What many electricians underestimate: the quality of the measurement depends critically on the measurement method used.
Why a Simple Resistance Measurement Is Not Enough
When an electrician measures the resistance of a ground electrode with a standard multimeter in 2-wire mode, they are not only measuring the ground electrode — they are also measuring the resistance of the two test leads, the contact resistances at the terminals, and all the contact surfaces of the instrument being used. With a 2-ohm ground electrode and 0.5 ohms of test lead resistance, the reading is 2.5 ohms — 25% too high. Conversely, stray voltage in the soil, flowing through neighboring networks or railway lines, can simulate a value that is too low. Both errors render the test worthless.
The 4-Wire Method (Fall of Potential)
The 4-wire earth ground tester GRT300 works according to the classic fall-of-potential method. Four connections are used: two for the test current and two separate ones for the voltage measurement. Since the voltage measurement is practically currentless, the lead resistances do not enter into the measured value. The result is the pure earth resistance — the value that must appear in the test documentation.
In practical measurement, two auxiliary earth electrodes (the auxiliary stake and the probe stake) are driven into the ground, typically at distances of 20 and 40 meters from the object under test. The instrument drives a defined current through the test object and the auxiliary stake and measures the voltage at the probe. From this configuration, the earth resistance is calculated using Ohm’s law — but with a decisive advantage: the measurement is insensitive to stray currents in the soil, because the measurement signal has a specific signature that is digitally filtered by the receiver.
What the Instrument Offers Technically
The GRT300 supports four measurement ranges: 2 / 20 / 200 / 2000 Ω. The lowest range is for high-quality grid earth electrodes in industrial installations with very low required resistance (< 1 Ω for lightning protection systems in exposed locations); the highest range is for rural residential installations and small grounding systems (up to 100 Ω permissible under DIN VDE 0100).
Automatic I- and P-spike testing: Before each measurement, the instrument checks whether the auxiliary electrodes are set correctly. If the contact resistance of an auxiliary electrode is too high (typical with very dry sandy soil or rock), a warning is issued — the measurement would otherwise be unreliable.
Autoranging and automatic zero adjustment: The instrument automatically selects the appropriate measurement range and compensates for internal offset errors. This reduces manual adjustment by the user to a minimum.
AC earth voltage measurement: In addition to the actual resistance measurement, the instrument records the AC voltage present between the ground electrode and remote earth. Stray voltage above approximately 10 V makes the actual measurement inaccurate and indicates network faults.
Two-line LCD: Simultaneous display of test current, voltage drop, and resulting earth resistance. The electrician can see at a glance whether the signal-to-noise ratio is sufficient for a reliable measurement.
Data hold and auto power-off function: The measured value is frozen so the electrician can note it down at leisure; the instrument switches itself off after a period of inactivity to conserve battery life.
Where the 4-Wire Tester Proves Its Value
Electrical installers: Acceptance testing of new installations under DIN VDE 0100 Part 610. Without a documented earth resistance, the installation cannot go into operation — and the documentation must be produced with a calibrated, specified instrument.
Periodic inspections (DGUV Regulation 3): Every four years for fixed installations, annually for portable equipment. A 4-wire tester is standard equipment in the test technician’s toolbox.
Lightning protection testing: Lightning protection systems require very low earth resistances (target value below 10 Ω, but often considerably lower under DIN EN 62305). Only a 4-wire instrument achieves the required accuracy in the lower resistance range.
Industrial installations: Chemical plants, filling stations, installations with high-power switching — all with special grounding requirements. Regular testing is a prerequisite for the operating permit.
Photovoltaic and wind power systems: DC systems and systems with rotating generators have special grounding requirements; regular re-measurement is part of the maintenance obligation.
Transmission masts and radio installations: RF grounding systems require very low resistance values; the 4-wire method is the only way to measure these precisely.
Church and historic building preservation: Historic buildings with retrofitted lightning protection systems require careful testing, as retrofitting often takes place in difficult ground conditions.
What the Kit Includes
The GRT300 kit contains all the components for complete field measurement: instrument with limited NIST calibration certificate, test leads with alligator clips, 4 auxiliary earth stakes (two auxiliary stakes plus two spares), a hard-shell case for rugged field use, and eight 1.5 V AA batteries for immediate readiness.
Cost-Effectiveness
At 1 630 euros, the instrument is an investment for an electrical installer or test technician that pays for itself after just a few accepted installations. Above all: the documentation produced by a 4-wire instrument is legally robust. In a follow-up inspection after a fault, no expert can call the measured values into question — and that is the true value of the instrument.